Raptor Smoke Alarm — Troubleshooting
Sales Portal Purchase Enquiries

Live Diagnosis

Walk through each step with the customer. Click an answer to reveal the next question.

Follow steps in order — each answer reveals the next question.
01Is the Alarm Currently Sounding or Flashing Red Rapidly?Active
Say to customer"Could you walk around and check each alarm? Is there any unit with a fast-flashing red light, or is any alarm actively beeping loudly right now?"

LED & Sound Indicators

Full reference — Raptor AS3786:2023 · RH638-AC-RF / RH638-B-RF

ConditionLEDSoundAction
Standby — AC mainsGreen solidNoneNormal
Standby — BatteryGreen 1× / 54 secNoneNormal
Test ModeRed rapid flash3 short quick beepsTest
Alarm — Smoke detectedRed rapid flash3 short quick beeps (loud, repeating)Urgent
Hush Mode
Button pressed during alarm
Red 1× / 10 secNone — silenced ~10 minMonitor
Alarm Memory
Triggered while absent — not a fault
Red 1× / 20 secNoneClear — Press button once
Low BatteryYellow 1× / 54 sec1 beep / 54 secReplace Unit
Sensor MalfunctionYellow 2× / 54 sec2 beeps / 54 secClean First — escalate if >1hr
End of Life
Unit is 10+ years old
Yellow 3× / 54 sec3 beeps / 54 secReplace Unit
ConditionHow to HushDurationLED During Hush
Active Alarm (nuisance)Press Test/Hush once~10 min, then auto-rearmsRed 1× / 10 sec
Low Battery chirpPress Test/Hush once12 hoursYellow 1× / 54 sec (silent)
Malfunction chirpPress Test/Hush once12 hoursYellow 2× / 54 sec (silent)
End of Life chirpPress Test/Hush once
Within 30 days of EOL only
~24 hoursYellow 3× / 54 sec (silent)

Networking & Pairing

Wireless interconnection — up to 40 alarms via RF433 · RH638-AC-RF / RH638-B-RF

ActionModeButton SequenceLED Indication
Enter pairing receive
On the HOST (existing) device
Code ReceivingPress 3× quickly (within 2 sec) → Long press 1 secGreen flash ~1 min — 1 beep per sub-device added
Enter pairing send
On the NEW (sub) device
Code SendingPress 2× quickly (within 1 sec) → Long press 1 secGreen flash ~8 sec, then on 3 sec + 1 beep = paired
Remove unit from groupNetwork ExclusionPress 4× quickly (within 2 sec) → Long press 1 secGreen flash 3 sec (2×/sec) then off
Full System TestRadio Link TestPress and hold 1 sec, then releaseAll paired alarms: Green flash + 6 beeps
Wireless Limits & Placement
Max wireless: 40 alarms — exceeding this may cause permanent damage.
Max wired: 20 alarms over 250 metres.
Open air range: ~150 metres between any two units. Steel and thick walls reduce range significantly.
Host placement: Centre of building acts as repeater. 2-storey: centre of main floor. 3-storey: centre of middle floor.
Pair one at a time: Do not run code learning on multiple units simultaneously.

Diagnostic Matrix

Quick-reference symptom → resolution lookup

SymptomDiagnosisFirst ActionIf Persists
Red rapid flash + loud beepingActive alarm — smoke or nuisanceHush Press once. Clean vents. Verify no fire.Escalate If re-sounds after hush
Red 1× / 20 sec — no beepAlarm memory — triggered recently, now normal. Not a fault.Clear Press button onceAuto-clears after 12 hours
Yellow 1× / 54 sec + 1 beepLow battery — sealed 10-yr lithium lowReplace Full unit replacement neededN/A — hush 12hr interim only
Yellow 2× / 54 sec + 2 beepsSensor malfunction — often dust/debrisClean Vacuum/brush all vent slotsEscalate If fault after 1hr
Yellow 3× / 54 sec + 3 beepsEnd of life — 10+ years oldReplace Cannot be fixed. Hush 24hr interim.N/A — replacement only
AC unit: no green lightLoss of mains powerBreaker Check/reset circuit breakerEscalate Electrician if breaker OK
Alarm not responding to link testNot paired or out of wireless rangeRe-pair See networking guideEscalate Reposition host or replace unit
Frequent nuisance alarmsPoor placement or dirty sensorClean Clean vents. Review install location.Relocate Too close to kitchen/bathroom/AC

Installation Locations

Reference for nuisance alarm relocation advice — AS3786:2023 manual

Recommended Locations
Between sleeping areas and potential fire sourcesHallway within 3m of any bedroom door Every level of a multi-storey homeNo more than 7.5m from the farthest wall or next alarm Centre of ceiling is idealIf wall-mounted: 300mm below ceiling On sloped/peaked ceilings: 900mm from the highest point
Avoid These Locations
Within 400mm of an AC vent or ceiling fanIn kitchens, boiler rooms, laundry rooms, or garages In very dusty or dirty areasWithin 300mm of light fittings or room corners Within 1500mm of fluorescent light fittingsAt the peak of an A-frame ceiling ("dead air" zone) In insect-infested areasNear ceiling decorations that block smoke path On poorly insulated walls or ceilingsOver stairwells or hazardous testing locations